Reverse Power Protection.
1- Protection against overspend 32G (# 1).
In case of Turbine Failure, the Turbine is tripped and then the Generator is tripped by operation of reverse power relay to prevent overspending of the Turbine generator unit.
2- Protection against generator motoring 32G (#2).
-Generator motoring protection is designed for the prime mover or the system, rather than for the generator.
- With steam turbines, Turbines will overheat on low steam flow, motoring results from a low input To the Ac Generator,
- When This I/P can’t meet all the losses, the deficiency is supplied by absorbing real power from the system.
- since field excitation should remain the same , the same reactive power would flow as before motoring , thus, on motoring the real power will be into the generator, while the reactive power may be either flowing out or into the generator
Setting of Reverse Power Relays
Data for setting calculations
-Rated Capacity of Generator -------- 440,000 KVA
-No Load Loss of Generator --------- 1,785 KW
-No Load Loss of Turbine ---------- 1,350 KW
-No Load Loss of TG unit ---------- 3,135 KW
-Permissible Motoring Time ------- 60 Sec.
-Relay Constant ------------------- 1 P.U. = Generator KVA
Setting Of Reveres Power Relay 32G ( #1 )
1- Reverse Power Trip Level
Trip Level < No load loss of TG unit * 0.3
= 3,135 * 0.3
= 940.5 KW
Pick up = Trip level / relay constant
= 941 / 440,000
= 0.0021 P.U.
Setting = - 0.002 P.U. ( 880KW )
2- Reverse Power Trip Delay
Trip Delay < Perm. Motoring time (60 Sec.)
Setting = 50 Cycles (1 Sec.)
Setting Of Reveres Power Relay 32G ( #2 )
1- Reverse Power Trip Level
Trip Level < No load loss of TG unit * 0.5
= 3,135 * 0.5
= 1,568 KW
Pick up = Trip level / relay constant
= 1,568 / 440,000
= 0.004 P.U.
Setting = - 0.004 P.U. ( 1,760KW )
2- Reverse Power Trip Delay
Trip Delay < Perm. Motoring time (60 Sec.)
Setting = 750 Cycles (15 Sec.)
Hi Hamza,
ReplyDeletehow does the reverse power relay operate? When the turbine trips, the power flow from generator will reduce and eventually stop. This will firstly be detected by Low Forward Power relay (37G)? Then what is the use of 32G? Can you explicitly explain if you have time or some of your associate can help.
Hamza bey iyi günler.ben Ferit.bir kamu kuruluşunda çalışıyorum.jeneratör parelellemelerinde ters güç koruması ile sorunlar yaşıyoruz ve bu sorunları gidermek için ters güç koruması yapan röleden yapmak istiyorum.yardımcı besleme 24vdc olacak.3 faz 440 volt 60 hz giriş olacak.ayrıca 1 akım trafosundan okuma yapabilecem.bu rölelerin temel prensibi nedir akım gerilim arasında ne gibi fark oluşması lazım ölçüm yöntemleri nelerdir.bunun için bana yardımcı olmanızı bekliyorum.iyi günler dilerim.
ReplyDeleteHamza bey iyi günler.ben Ferit.bir kamu kuruluşunda çalışıyorum.jeneratör parelellemelerinde ters güç koruması ile sorunlar yaşıyoruz ve bu sorunları gidermek için ters güç koruması yapan röleden yapmak istiyorum.yardımcı besleme 24vdc olacak.3 faz 440 volt 60 hz giriş olacak.ayrıca 1 akım trafosundan okuma yapabilecem.bu rölelerin temel prensibi nedir akım gerilim arasında ne gibi fark oluşması lazım ölçüm yöntemleri nelerdir.bunun için bana yardımcı olmanızı bekliyorum.iyi günler dilerim.
ReplyDeleteThe short trip time requires a turbine trip signal to also be present so no point waiting.
ReplyDeleteThe long time allows for governor action to recover